The Micropilot S measuring instrument requires no special maintenance.
Exterior cleaning
When cleaning the exterior of measuring devices, always use cleaning agents that do not attack the
surface of the housing and the seals.
Replacing seals
The process seals of the sensors must be replaced periodically, particularly if molded seals
(asepticconstruction) are used. The period between changes depends on the frequency of cleaning
cyclesand on the temperature of the measured product and the cleaning temperature.
Repair
The Hauser repair concept assumes that the measuring devices have a modular design and
that customers are able to undertake repairs themselves. Spare parts are contained in suitable kits.
They contain the related replacement instructions. All the spare parts kits which you can order from
Hauser for repairs to the Micropilot s are listed with their order numbers on Page 77 ff..
Please contact Hauser Service for further information on service and spare parts.
Repairs to Ex-approved devices
When carrying out repairs to Ex-approved devices, please note the following:
• Repairs to Ex-approved devices may only be carried out by trained personnel or
byHauser Service.
• Comply with the prevailing standards, national Ex-area regulations, safety instructions (XA)
andcertificates.
• Only use original spare parts from Hauser.
• When ordering a spare part, please note the device designation on the nameplate. Only
replaceparts with identical parts.
• Carry out repairs according to the instructions. On completion of repairs, carry our the
specifiedroutine test on the device.
• Only Hauser Service may convert a certified device into a different certified variant.
• Document all repair work and conversions.
Replacement
After a complete Micropilot or electronic module has been replaced, the parameters can
bedownloaded into the instrument again via the communication interface. Prerequisite to this is
that the data were uploaded to the PC beforehand using FieldCare.
Measurement can continue without having to carry out a new setup.
• You may have to activate linearisation (see BA217F on the enclosed CD-ROM).)
• You may need to record the tank map again (see Basic Setup)
After an antenna component or electronic has been replaced, a new calibration must be carried out.
This is described in the repair instructions.
Summary of Contents for Micropilot S FMR531
Page 4: ...Brief overview Micropilot S FMR531 with HART 4 20 mA 4 Endress Hauser ...
Page 87: ...Micropilot S FMR531 with HART 4 20 mA Technical data Endress Hauser 87 ...
Page 98: ...Micropilot S FMR531 with HART 4 20 mA Index 98 Endress Hauser ...
Page 100: ...www endress com worldwide BA207F 00 en 04 09 71093754 CCS FM SGML 6 0 ProMoDo 71093754 ...