23
Reference Manual
00809-0100-4853, Rev AB
Installation
January 2017
Installation
3.4.2
Tagging
Commissioning (paper) tag
To identify which device is at a particular location use the removable tag provided with the transmitter.
Ensure the physical device tag (PD tag field) is properly entered in both places on the removable
commissioning tag and tear off the bottom portion for each transmitter.
Figure 3-5. Commissioning Tag
3.4.3
Consider housing rotation
To improve field access to wiring or to better view the optional LCD display:
1. Loosen the housing rotation set screw.
2. Turn the housing up to 180° left or right of its original (as shipped) position.
3. Re-tighten the housing rotation set screw to 30 in-lb.
Figure 3-6. Transmitter Housing Set Screw
A. Housing rotation set screw (
3
/
32
-in.)
Note
Do not rotate the housing more than 180° without first performing a disassembly procedure.
Over-rotation may sever the electrical connection between the sensor module and the electronics.
Commissioning Tag
DEVICE ID:
001151AB00010001440-121698091725
DEVICE REVISION: 1.0
PHYSICAL DEVICE TAG
DEVICE ID:
001151AB00010001440-121698091725
DEVICE REVISION: 1.0
S / N :
PHYSICAL DEVICE TAG
Device Barcode
A