51
Reference Manual
00809-0100-4853, Rev AB
Troubleshooting
January 2017
Troubleshooting
Process
Temperature
Sensor Failure
FAIL
PT
ERROR
Failure has been detected in the
process temperature sensor
1. Verify the conditions of the process where the transmitter is
installed.
Note: If a junction box is installed/utilized, check the connections for the RTD
sensor.
2. Remove back housing cover (considering hazardous location
requirements) and check the cable and cable connection
between terminal block and RTD sensor.
3. Replace the RTD sensor.
4. Replace the electronic circuit board.
Table 5-4. Out of Specification–Fix Soon
Alert label
LCD
display
message
Description
Recommended action
Differential
Pressure Out of
Limits
DP
LIMIT
Differential pressure
has exceeded the
transmitter's
maximum
measurement range
1. Verify conditions of the process where the transmitter is installed.
2. Check transmitter pressure connection to make sure it is not plugged and
isolating diaphragms are not damaged.
3. Replace the sensor module.
Static Pressure
Out of Limits
AP GP
LIMIT
Static pressure has
exceeded the
transmitter's
maximum
measurement range
1. Verify conditions of the process where the transmitter is installed.
2. Check transmitter pressure connection to make sure it is not plugged and
isolating diaphragms are not damaged.
3. Replace the sensor module.
Process
Temperature
Out of Limits
PT
LIMIT
Process temperature
has exceeded the
transmitter's
maximum
configured
measurement range
1. Verify conditions of the process where the transmitter is installed.
Note: If a junction box is installed/utilized, check the connections for the RTD sensor.
2. Remove back housing cover (considering hazardous location requirements)
and check the cable and cable connection between terminal block and the
RTD sensor.
3. Replace the RTD sensor.
4. Replace the electronic circuit board.
Module
Temperature
Out of Limits
SNSRT
LIMIT
Module temperature
sensor has exceeded
its normal range
1. Check process and ambient temperatures where the transmitter is installed to
ensure they are within specifications.
2. Replace the sensor module.
Table 5-3. Failed–Fix Now
Alert label
LCD
display
message
Description
Recommended action
Summary of Contents for Rosemount MultiVariable 3051SMV
Page 2: ......
Page 6: ...vi Reference Manual 00809 0100 4853 Rev AB Contents January 2017 Contents ...
Page 44: ...36 Reference Manual 00809 0100 4853 Rev AB Installation January 2017 Installation ...
Page 62: ...54 Reference Manual 00809 0100 4853 Rev AB Troubleshooting January 2017 Troubleshooting ...
Page 111: ......