48
Reference Manual
00809-0100-4853, Rev AB
Troubleshooting
January 2017
Troubleshooting
5.3
Measurement troubleshooting
The transmitter provides a means to display the current process variables and flow calculations. If the
process variable reading is unexpected, this section provides the symptoms and possible corrective
actions.
Table 5-1. Unexpected Process Variable (PV) Readings
Symptom
Corrective action
High PV
Reading, Erratic
PV Reading,
Low or no PV
reading
Primary element
•
Check for restrictions at the primary element.
•
Check the installation and condition of the primary element.
•
Note any changes in process fluid properties that may affect output.
Impulse piping
•
Check to ensure the pressure connection is correct.
•
Check for leaks or blockage.
•
Check to ensure that blocking valves are fully open.
•
Check for entrapped gas in liquid lines or for liquid in gas lines.
•
Check to ensure the density of fluid in impulse lines is unchanged.
•
Check for sediment in the transmitter process flange.
•
Make sure that process fluid has not frozen within the process flange.
Power supply
•
Check the output voltage of the power supply at the transmitter. It should be 9 to 30 V dc (9 to
17.5 V dc for FISCO)
Flow configuration (fully compensated mass flow feature board only)
•
Verify flow configuration is correct for current application
Process temperature RTD input
•
Verify the PT Mode (Normal, Fixed, Back-up)
•
Verify the correct Callendar-Van Dusen
coefficients
•
Verify all wire terminations
•
Verify sensor is a Pt 100 RTD
•
Replace Pt 100 sensor
Sensor module
•
Check for obvious defects, such as a punctured isolating diaphragm or fill fluid loss, and if
replacement is needed, contact the nearest Emerson Service Center.
•
Check for proper fill fluid characteristics (see
for more information).
Summary of Contents for Rosemount MultiVariable 3051SMV
Page 2: ......
Page 6: ...vi Reference Manual 00809 0100 4853 Rev AB Contents January 2017 Contents ...
Page 44: ...36 Reference Manual 00809 0100 4853 Rev AB Installation January 2017 Installation ...
Page 62: ...54 Reference Manual 00809 0100 4853 Rev AB Troubleshooting January 2017 Troubleshooting ...
Page 111: ......