7
Reference Manual
00809-0100-4853, Rev AB
Configuration
January 2017
Configuration
Depending on the fluid selected, Engineering Assistant 5.5.1 ver. 2 may bring up a screen for entering
additional fluid information.
4. Select a primary element type, then enter the sizing information in the fields provided.
5. Select
Next
.
6. Enter the operating conditions for the fluid.
a. Select the pressure and temperature range based on the operating conditions of the process, not
the sensor range of the transmitter.
Note
An extremely large or small operating range may increase the uncertainty of the flow calculation.
The units used for flow configuration are only used in the Engineering Assistant software. For
configuration of device variable units, see
“Units configuration” on page 10
7. Enter the atmospheric pressure.
The transmitter needs absolute pressure to calculate flow. If gage pressure is measured, the transmitter
will calculate absolute pressure based on the user-defined atmospheric pressure. Atmospheric pressure
can be changed in the screen below. This setting may also be configured per the atmospheric offset
configuration (see
) in the Sensor Transducer Block.