Level is stuck in measuring range
Figure 7-2: Symptom
A
B
C
D
A. Level
B. Time
C. Actual level
D. Reported level
Possible cause
Disturbing object in the tank.
Recommended actions
•
Use the suppress false echoes function to manage strong disturbance echoes.
•
Analyze the echo curve and check amplitude thresholds.
•
Remove the disturbing object.
•
Put an inclined metal plate on top of the disturbing object.
•
Move the transmitter to another position.
Related information
Suppressing false echoes
Read the echo curve
Amplitude threshold
Installation considerations
Reference Manual
Service and troubleshooting
00809-0100-4418
September 2022
Rosemount 3408 Level Transmitter
71