4. If not needed, disable this alert.
Related information
7.2.14
Low user defined alert
Category
Maintenance Required
Cause
The user defined variable is below the defined limit.
Recommended actions
1. Bring the system to a safe state.
2. Verify that the process variable is within specified limits.
3. Reconfirm the user defined alarm limit.
4. If not needed, disable this alert.
Related information
7.2.15
Linearized variable out of range
Category
Maintenance Required
Cause
The level measurement is outside the configured range for volume or scaled variable, or
both.
Accuracy of volume/scaled variable measurement may be degraded.
Recommended actions
1. If volume strapping table is used, make sure level values within operating range
are included.
2. If scaled variable table is used, make sure input variable values within operating
range are included.
Related information
7.2.16
Dielectric constant estimation degraded
Category
Maintenance Required
Reference Manual
Service and troubleshooting
00809-0100-4418
September 2022
Rosemount 3408 Level Transmitter
67