6
Operation and maintenance
6.1
Variable screens
The transmitter can display the following variables:
Table 6-1: LCD Display Variables
Parameter
Presentation on display
Description
Level
LEVEL
The current level measurement value.
Distance
DISTANCE
Distance from the upper reference
point to the product surface.
Level rate
LEVEL RATE
The current velocity at which the level
is moving. A positive value indicates
the surface is moving up.
Signal strength
SIG STRENGTH
The signal amplitude of the surface
echo.
Volume
VOLUME
Volume of the product at the current
level.
Electronics temperature
ELECTRONICS
The current temperature at the
electronics.
Signal quality
SIGNAL QUALITY
The quality of product surface echo
signal compared to surface threshold
and noise.
Scaled variable
SCALED VARIABLE
A variable calculated from a scaling
table (as defined by pairs of input/
scaled values).
Percent of range primary
variable
% OF RANGE PV
A variable value expressed in percent
within a range defined by a Lower
Range Value (LRV) and an Upper
Range Value (URV).
Auxiliary percent of range
% OF RANGE AUX
A variable value expressed in percent
within a range defined by the lower
and upper range values (0% Auxiliary
and 100% Auxiliary).
A variable associated with a selected
register in the device.
Loop current
ANALOG OUT
Loop current as perceived by the
device.
(1)
Only for transmitters ordered with Smart Diagnostics Suite.
(2)
Default, user selectable display text (up to 14 characters).