Service Menu Parameters
Liebert
®
iCOM
®
for Liebert DSE
™
134
Figure 111
Set alarms screen, page 3 of 12
S224 Customer Input 1, 2, 3 & 4
—Select the device and operation of the customer inputs. Each
event reflects a different alarm and possible action to the unit. Refer to
selectable options.
S225-231 Customer Input 1, 2, 3 & 4 active when
—Select whether the input is a normally closed
or normally closed input.
S232 Warning Activates Alarm Relay
—Sets the alarm relay (K3) to activate when a warning
occurs.
S233 Water Alarm Shuts Unit Down
—Turn the unit Off if a water alarm occurs.
Set Alarm Screens, Pages 4-12
The Set Alarm Screens, pages 4 through 12 (
) permit setting the operation
of an active alarm. Each event can be enabled or disabled and can be set to operate as an alarm,
warning or message. The delay is the time the control waits before reporting the event.
Alarm
: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes
the red LED on the display.
Warning
: Annunciates the buzzer, triggers a monitoring event, shows the event in the event
viewer / front display and flashes the red LED on the display.
Message
: Shows the event in the event viewer and on the front display.
Delay
—The delay selection for each alarm.
EN-DIS
—The enable / disable selection for each alarm provides the ability to individually select the
alarms that will or will not activate when the alarm condition occurs.
Type
—Sets the type of action for each event listed. There are three different types of events: Alarm,
Warning and Message. When an event is triggered and the type is set to “Alarm,” then the light and
buzzer on the display will activate, an event will be written to the event log and the (K3) alarm relay
will close. If the type is set to “Warning,” then the light and buzzer on the display will activate, an
event will be written to the event log and the (K3) alarm relay can be configured to close or provide no
reaction. If the type is set to “Message,” then the event is only written to the event log.