Operation
61
Liebert
®
iCOM
®
for Liebert DSE
™
Table 14
Liebert EconoPhase events and alarm notifications on Liebert DSE models
Event
Description
PB1 BOARD FAIL
An unrecoverable fatal system error has occurred. Pump shut down. Pump board must be
rebooted to reset event.
PB1 CAVITATE SHUTDOWN Pump has cavitated and was shut down. Event is reset when the Liebert iCOM requests a
new startup.
PB1 IN PRES SENS FAIL
Inlet refrigerant pressure sensor failure. Pump shut down. Event is reset when condition
clears.
PB1 IN TEMP SENS FAIL
Inlet refrigerant temperature sensor failure. Pump shut down. Event is reset when condition
clears.
PB1 INV DATA SHUTDOWN
Invalid data detected and pump was shut down. Event is reset when the Liebert iCOM
requests a new startup.
PB1 LO DIFF PRESSURE
Pump differential pressure fell below a lower threshold and pump was shut down. Event is
reset when the Liebert iCOM requests a new startup.
PB1 LO OUTLET TEMP
Pump outlet refrigerant temperature fell below a lower threshold and pump was shut down.
Event is reset when the Liebert iCOM requests a new startup.
PB1 OUT PRES SEN FAIL
Outlet refrigerant pressure sensor failure. Pump shut down. Event is reset when condition
clears.
PB1 OUT TEMP SEN FAIL
Outlet refrigerant temperature sensor failure. Pump shut down. Event is reset when condition
clears.
PB1 CAN DISCONNECTED
iCOM lost CAN communications with pump board. Pump shut down. Event is reset when
condition clears.
PB1 REMOTE SHUTDWN
Remote shutdown alarm state. Pump shut down. Event is reset when condition clears.
PB1 STARTUP FAIL
Three pump startups in a row have failed. Event must be manually reset by user.
PB2 BOARD FAIL
An unrecoverable fatal system error has occurred. Pump shut down. Pump board must be
rebooted to reset event.
PB2 CAVITATE SHUTDOWN Pump has cavitated and was shut down. Event is reset when the Liebert iCOM requests a
new startup.
PB2 IN PRES SENS FAIL
Inlet refrigerant pressure sensor failure. Pump shut down. Event is reset when condition
clears.
PB2 IN TEMP SENS FAIL
Inlet refrigerant temperature sensor failure. Pump shut down. Event is reset when condition
clears.
PB2 INV DATA SHUTDOWN
Invalid data detected and pump was shut down. Event is reset when the Liebert iCOM
requests a new startup.
PB2 LO DIFF PRESSURE
Pump differential pressure fell below a lower threshold and pump was shut down. Event is
reset when the Liebert iCOM requests a new startup.
PB2 LO OUTLET TEMP
Pump outlet refrigerant temperature fell below a lower threshold and pump was shut down.
Event is reset when the Liebert iCOM requests a new startup.
PB2 OUT PRES SEN FAIL
Outlet refrigerant pressure sensor failure. Pump shut down. Event is reset when condition
clears.
PB2 OUT TEMP SEN FAIL
Outlet refrigerant temperature sensor failure. Pump shut down. Event is reset when condition
clears.
PB2 CAN DISCONNECTED
iCOM lost CAN communications with pump board. Pump shut down. Event is reset when
condition clears.
PB2 REMOTE SHUTDWN
Remote shutdown alarm state. Pump shut down. Event is reset when condition clears.
PB2 STARTUP FAIL
Three pump startups in a row have failed. Event must be manually reset by user.
PB1 COMMUNICATE FAIL
Ethernet communications failure. Pump not shut down. Event is reset when condition clears.
USB communications failure. Pump not shut down. Event is reset when condition clears.
PB2 COMMUNICATE FAIL
Ethernet communications failure. Pump not shut down. Event is reset when condition clears.
USB communications failure. Pump not shut down. Event is reset when condition clears.
PB1 COND TO PUMP TEMP
Temperature variance from condenser 1 output to pump 1 input exceeds allowable
parameters.
PB2 COND TO PUMP TEMP
Temperature variance from condenser 2 output to pump 2 input exceeds allowable
parameters.