Service Menu Parameters
Liebert
®
iCOM
®
for Liebert DSE
™
154
Figure 139
Options setup, page 2 of 6
S413 Humidification Enabled
—Enables or disables humidification.
S414 Infrared Flush Rate
—Shows the amount of makeup water supplied to an infrared humidifier
as a percentage of the humidifier capacity. This value can be set from 110-500% (default is 150%).
Higher flush rates reduce mineral deposit buildup in the humidifier pan.
S415 Humidifier Steam Rate
(Liebert HPM
™
and Liebert PeX
™
only)—Reduces humidifier
capacity to be a percentage of nominal humidifier capacity on units with variable capacity steam
bottle humidifiers.
S416 Humidifier Control
—Used for Liebert HPM and Liebert PeX units only.
S417 Humidifier Bottle Flush Time
—Used for Liebert HPM and Liebert PeX units only.
S418 Humidifier Bottle Manual Flush
—Used for Liebert HPM and Liebert PeX units only.
S419 Dehum Enabled/Dehum Fan Ctrl
—Selects whether the compressor and / or valve will be
used to dehumidify when the humidity is above setpoint.
S420 Auto Restart Enabled
—Restarts the unit after a power cycle when set to “Yes.” When this
parameter is set to “No,” the unit will not restart (Turn On) after a power cycle.
S421 Single Unit Auto Restart
—Sets a time delay for the unit to restart when the Auto Restart
Enabled is set to “Yes”. The delay begins once the boot process has completed. This parameter allows
units to be staggered On to reduce the amount of simultaneous power consumption after a loss of
power.
S422 On-Off Enabled
—Sets the Liebert iCOM control to ignore the On/Off command from the
display On/Off button when set to NO. This parameter is a local setting in the control board.
S42A Fan Shutdown Delay Timer
—Sets the fan shutdown delay timer to allow the fan to continue
to operate after the unit has been shut down. This parameter is adjustable from 0 - 999 seconds. The
default setting is 0 seconds.