Operation
59
Liebert
®
iCOM
®
for Liebert DSE
™
FC LOCKOUT
2 Sec
2 sec / 0 – 9999 *
WRN
COMPRESSOR(S) LOCKOUT
2 Sec
2 sec / 0 – 9999 *
WRN
COMP 1 SHORT CYCLE
0 Sec
0 - 9999
MSG
COMP 2 SHORT CYCLE
0 Sec
0 - 9999
MSG
No Power
0
0 seconds / 0-9999
WRN
Condensate 1 Failure
0
5 seconds / 0-9999
WRN
Condensate 2 Failure
0
5 seconds / 0-9999
WRN
EC Fan Fault
0
10 seconds / 0-9999
ALM
HIGH SUP TEMP
0
30 seconds / 0-9999
WRN
LOW SUP TEMP
0
30 seconds / 0-9999
ALM
REDUCED ECO AIRFLOW
0
3 seconds / 0-9999
WRN
ECO HI TEMP OVERRIDE
0
10 seconds / 0-9999
WRN
TEMP CTRL SENSOR FAIL
0
3 seconds / 0-9999
ALM
HIGH DEW POINT
0
30 seconds / 0-9999
WRN
LOW DEW POINT
0
30 seconds / 0-9999
WRN
HI DEW POINT SENSOR A
0
30 seconds / 0-9999
WRN
LOW DEW POINT SENSOR A
0
30 seconds / 0-9999
WRN
HIGH REMOTE SENSOR
0
30 seconds / 0-9999
WRN
POWER “A” FAILURE
0
10 seconds / 0-9999
ALM
POWER “B” FAILURE
0
10 seconds / 0-9999
ALM
AIRFLOW SENSOR FAILURE
0
10 seconds / 0-9999
WRN
HUM CTRL SENSOR FAIL
0
30 seconds / 0-9999
WRN
LOSS OF FLOW
0
5 seconds / 0-9999
ALM
STAT PRES SENSOR FAIL
0
120 seconds / 0-9999
ALM
LOW STATIC PRESSURE
0
120 seconds / 0-9999
WRN
HIGH STATIC PRESSURE
0
120 seconds / 0-9999
WRN
STATPRES OUT OF RANGE
0
150 seconds / 0-9999
WRN
DAMPER FAILURE
0
10 seconds / 0-9999
ALM
BMS DISCONNECTED
0
ENABLED / DIS - ENAB
WRN
Table 12
Possible event settings—events listed may vary by specific unit and options order
Event
Internal Delay
(Before Action Occurs)
Default Delay / Selectable
(Before Action Occurs)
Type
(default)