Operation
63
Liebert
®
iCOM
®
for Liebert DSE
™
Table 16
Customer inputs
Setting
Reaction
Smoke
Event Only
Water Alarm
Event Only
C PMP Alarm
Event Only
Flow Alarm
Event Only
Stdby G Pmp
Event Only
Stdby Unit
Event Only
C-Input 1
Event Only
C-Input 2
Event Only
C-Input 3
Event Only
C-Input 4
Event Only
Rht Lockout
Event + Electrical Heaters Disabled
Hum Lockout
Event + Humidifier Disabled
Rht+Hum Lock
Event + Electrical Heaters and Humidifier Disabled
Comp Lockout
Event + Compressor(s) Disabled w/o Pump Down
Call Service
Event Only
High Temp
Event Only
Air Loss
Event Only
FC Lockout
Event + Free Cooling Disabled
Heater Alarm
Event + Heaters Off (Liebert PeX
™
Only)
Flow AL SD
Event + Shut Down the Unit
Flow AL LC
Event + Lockout Compressors, No Pump Down (enabled only if at least one compressor is
on; auto-reset depends on input status)
Comp Lock PD
Event + Compressor(s) Disabled w/ Pump Down
Enable FC
Forces Free Cooling to On
HTRJ VFD
Activates the HEAT REJ VFD ALARM; no other function
HTRJ TVSS
Activates the HEAT REJ TVSS ALARM; no other function
FIRE ALARM
Event + Shuts The Unit Down
2
ND
SETPOINT
No Event But Switches To The Second Setpoint
NO POWER
Event + Disables Unit
LSI
Event + Activates Cylinder Worn And Stop Filling Bottle When Full
COND 1 FAIL
Event Only
COND 2 FAIL
Event Only
D-SCROLL RED
Event + Reduces The Requested Compressor Capacity By 20%
SWAP VALVE
No Event -active X Valve Closes And Y Opens / Inactive Y Closes And X Opens
EC FAN FAULT
Event + Sets Analog Output To 10v
ECO AIRFLOW
Event + Reduces Economizer Airflow
DAMPERSWITCH
End Switch
POWER A
Event Only
POWER B
Event Only