User Menu Parameters
Liebert
®
iCOM
®
for Liebert DSE
™
98
U304 Optional Sensor B2H
—Shows the Sensor B humidity value if optional reference sensor is
connected to the Liebert iCOM controller area network (CAN) bus. A reference sensor can be connected
to any type of Liebert iCOM unit. When an optional temperature and humidity or the optional 2T
sensor is connected and set as Sensor B, then its value will be displayed on this line. Liebert iCOM will
auto detect what type of sensor is connected. Sensor B can only be used as a reference sensor for
reading and monitoring but not for control purposes. Sensor B is selected by setting the DIP switches
on the temperature and humidity board. Refer to manual for the correct settings.
U305 Optional Sensor C1T
—Shows the Sensor C temperature value if optional reference sensor is
connected to the Liebert iCOM controller area network (CAN) bus. A reference sensor can be
connected to any type of Liebert iCOM unit. When an optional temperature and humidity or the
optional 2T sensor is connected and set as Sensor C, then its value will be displayed on this line.
Liebert iCOM will auto detect what type of sensor is connected. Sensor C can only be used as a
reference sensor for reading and monitoring but not for control purposes. Sensor C is selected by
setting the DIP switches on the temperature and humidity board. Refer to manual for the correct
settings. This sensor setting is also used as the outdoor sensor in Air Economizer Applications.
U306 Optional Sensor C2
H—Shows the Sensor C humidity value if optional reference sensor is
connected to the Liebert iCOM controller area network (CAN) bus. A reference sensor can be
connected to any type of Liebert iCOM unit. When an optional temperature and humidity or the
optional 2T sensor is connected and set as Sensor C, then its value will be displayed on this line.
Liebert iCOM will auto detect what type of sensor is connected. Sensor C can only be used as a
reference sensor for reading and monitoring not for control purposes. Sensor C is selected by setting
the DIP switches on the temperature and humidity board. Refer to manual for the correct settings.
This sensor setting is also used as the outdoor sensor in Air Economizer Applications.
U307 Freecooling Fluid Temperature
—Displays the temperature of the incoming water on units
equipped with a free-cooling coil.
U308 Outdoor Temperature
—Reads the outdoor temperature for free-cooling and dual cool units
to determine if cooling can be provided without compressor operation. It is determined by comparing
the temp between the room and outdoor air temperature. Available only on Liebert HPM
™
units.
U309 Freecooling Status
—Displays whether free-cooling is available for use, based on the return
air temperature and the incoming fluid temperature.
U310 DigiScroll 1/2 Temperature
—Shows the actual digital scroll number 1 discharge
temperature on units with digital scroll compressors.
U311 Current Static Pressure
—Status of the current static pressure of the unit.
U312 Current SYS Static Pressure
—Status of the system static pressure where multiple static
pressure sensor are shared across the team work network.
U31A Calculated Airflow
—Status shows the calculated airflow based on an installed differential
pressure transducers.
Figure 73 Sensor data screen, page 2 (return only)