Operation
Liebert
®
iCOM
®
for Liebert DSE
™
52
Low Noise / Fan Reversal
Fan reversal interval should be programmed at times when the unit is off (monitoring off, standby or
Remote Shut Down (RSD)).
Liebert iCOM (apart from the configuration and status screens) has to perform two timer activities:
• Low noise during programmed days / time (common for dual Liebert MC boards).
• Fan reversal in a specified frequency (allows separate settings for dual Liebert MC boards).
Figure 41 User-Condenser Timer, pages 1 and 2
U802 Low Noise Timer Enabled—
Sets the low noise operations of the condenser fan. When the
parameter is set to “YES,” the low noise operation is selected. When set to “NO,” the low noise will be
disabled even if a schedule is set below. Low noise may be overridden by calculated gain sequence at
the Liebert MC to prevent a high-pressure situation.
U803 Noise Reduction On—
Lists the day(s) that low noise feature can be scheduled if U802 is set
to “YES”.
U804 Whole Days—
Selects the whole day(s) low noise operations will be available for the condenser
fan. When the parameter is set to “YES,” the low noise operation is selected for the whole day. When
set to “NO” the low noise will be disabled.
U805 Interval Days—
Selects the interval day(s) low noise operations will be available for the
condenser fan. When the parameter is set to “YES” the low noise operation is selected. When set to
“NO” the low noise will be disabled even if an interval time is set below.
U806 Interval From—
Selects the time of day that the low noise feature will be enabled between
00:00 and 24:00.
U807 Operating Mode (0=LN, 100=HE)—
The first value represents the fan speed during low noise
operation. The second value represents the fan speed during normal or high efficiency operation. The
first value is linked to U818 and the second to U819.
U813 Select Condenser 2—
This menu selection toggles between condenser 1 and 2. When “Select
Condenser 2” is shown, the data below is for condenser 1. When “Select Condenser 1” is shown, the
data below is for condenser 2.
U814 Fan Reversal Every x Days—
Selection defines the numbers of days between fan reversals.
This parameter is adjustable from 1-100 days. The default set value is 0 days = OFF. Fan reversal can
only be performed with both compressors satisfied. Fan reversal interval should be performed during
standby periods. If the compressor is operating, the control will skip the scheduled reversal and retry
the next interval day. If the scheduled fan reversal is missed, the control will look for the next
available time to do a fan reversal where the compressor’s calls are met and initiate the reversal.
U815 Reverse Fan At:—
Selection defines what time the fan reversal will be performed in 00:00 to
24:00.