Service Menu Parameters
129
Liebert
®
iCOM
®
for Liebert DSE
™
Figure 105
Diagnostics/service mode screen, page 5 of 8
Status Remote Shutdown
—Shows the status of the unit’s remote shut down input.
S346 Status Airflow Loss
—Shows the status of the unit’s air proof switch.
S347 Status Motor Overload / EC Fan Fault
—Shows the status of the unit’s main fan overload or
EC fan fault input.
S348 Status Filter
—Shows the status of the unit’s filter clog switch input.
S349-352 Status Customer Input 1, 2, 3 & 4
—Shows the status of the unit’s customer inputs.
S353 Status Heaters Safety—
Status shows the safety heaters switch.
S354 Loss of Airflow At
—Sets the airflow at which the Loss of Airflow is activated. This parameter
is adjustable from 0 to 100%. The default setting is 40%.
S355 Actual Airflow
—Status shows the actual airflow based in percentage from 0-100%.