Service Menu Parameters
141
Liebert
®
iCOM
®
for Liebert DSE
™
8.7
Service-Sensor Calibration Menu Screens
Sensor Calibration allows the user to view readings of connected sensors and calibrate values as
needed.
Figure 124
Sensor calibration setup screen, page 1 of 7 (standard and tandem compressors)
S602 Return Temperature
—Adjusts the return temperature reading from the actual sensor to
compensate for any error of the sensor or to match other sensors in the room.
S603 Calibrated Return Temperature
—Shows the adjusted temperature value of the return
sensor. This value is the actual sensor reading (plus or minus) the offset “Return Temperature”.
S604 Return Humidity
—Adjusts the return humidity reading from the actual sensor to compensate
for any error of the sensor or to match other sensors in the room.
S605 Calibrated Return Humidity
—Shows the adjusted humidity value of the return sensor. This
value is the actual sensor reading (plus or minus) the offset “Return Humidity”.
S606 DigiScroll 1 NTC
—Adjusts the Digital Scroll 1 NTC reading from the actual sensor to
compensate for any error or drift of the sensor.
S606 DigiScroll 1A NTC
—
Tandem Compressors Only.
Adjusts the Digital Scroll 1A NTC reading
from the actual sensor to compensate for any error or drift of the sensor.
S607 Calibrated Digiscroll 1 NTC
—Shows the adjusted Digital Scroll 1 NTC sensor value. This
value is the actual sensor reading (plus or minus) the offset on line 606 “Digital Scroll 1 NTC”.
S607 Calibrated Digiscroll 1B / 1A NTC
—
Tandem Compressors Only.
Shows the adjusted Digital
Scroll 1B/1A NTC sensor value. This value is the actual sensor reading (plus or minus) the offset on
line 606 “Digital Scroll 1A NTC”.
S608 Digiscroll 2 NTC
—Adjusts the Digital Scroll 1 NTC reading from the actual sensor to
compensate for any error or drift of the sensor.
S608 Digiscroll 2A NTC
—
Tandem Compressors Only.
Adjusts the Digital Scroll 2A NTC reading
from the actual sensor to compensate for any error or drift of the sensor.
S609 Calibrated Digiscroll 2 NTC
—Shows the adjusted Digital Scroll 2 NTC sensor value. This
value is the actual sensor reading (plus or minus) the offset “Digital Scroll 1 NTC.”
S609 Calibrated Digiscroll 2B / 2A NTC
—
Tandem Compressors Only.
Shows the adjusted Digital
Scroll 2A NTC sensor value. This value is the actual sensor reading (plus or minus) the offset “Digital
Scroll 2A NTC.”
Standard Compressor Screen
Tandem Compressor Screen
(Compressor 1 & 2B temperature calibration
through Liebert iCOM is not currently supported)
Summary of Contents for Liebert iCOM
Page 2: ......
Page 169: ...Service Menu Parameters 161 Liebert iCOM for Liebert DSE Notes ...
Page 170: ...Service Menu Parameters Liebert iCOM for Liebert DSE 162 ...
Page 171: ......