Liebert iCOM Display Components and Functions
Liebert
®
iCOM
®
for Liebert DSE
™
8
Unit Screen with EconoPhase View
The unit screen with EconoPhase View provides a summary of individual unit operations including
return and supply temperatures, EconoPhase Status, Pump Status, and other key information to the
EconoPhase circuit.
Figure 8
Unit Screen with EconoPhase View
Table 2
Liebert EconoPhase status
EconoPhase Status
Status Description
Normal Operation
PRE mode is active (pumps may be on or off).
PB Comms Error
PRE pump board comms error.
GC Comms Error
GC board comms error.
EEV Comms Error
EEV board comms error.
Pump Recovery Time
Temporary pump failure (will try later).
Pump Cycle Lock-Out
Lock-Out too many pump-to-compressor transitions @ cold ambient.
Outdoor Temp Too High
Outside Temperature too high for PRE pump operation.
Unit Is Off
Unit is OFF (no cooling, heating, etc.).
Transitioning to PRE Mode
Transition to PRE, waiting for the compressor to stop.
Pump Failure
Permanent pump failure.
Not Configured for Operation
The Pump has not been enabled.
Sensor Reading(s) Invalid
Liebert Microchannel ambient or iCOM control (supply, remote, or return) error.
Other
Waiting for other circuit
Compressor Dehum Op
Dehumidification operation has priority over Mixed/Pump at this time.
Waiting for Reduced Cntrl Temp
Control temperature too high to start the pump.
EconoPhase
Operation State
Pumps 1 and
2 Status
Return Air
Temperature
Supply Air
Temperature
EconoPhase
Pump Speed
and Differential
Pressure
Highest Outdoor
Temperature
Sensed by
Connected
Liebert MC
Supply Air
Temperature
Suction Refrigerant
Temperature for
Each Loop
Pump Discharge
Refrigerant
Temperature for
Each Loop