Service Menu Parameters
113
Liebert
®
iCOM
®
for Liebert DSE
™
S160 Fanspeed Reposition Mode/Delay Decel/
—This parameter should only be adjusted by a
factory service trained technician. The fan speed reposition mode / delay is a one time delay as the fan
speed is requested to change direction. This delay will be applied only when the fan speed is
commanded from an increasing to decreasing state or a decreasing to increasing state. This allows the
fan to hold its current position while the temperature stabilizes.
S161 Max Deceleration Rate
—This parameter should only be adjusted by a factory service trained
technician. Only slows the decreasing of the variable fan speed. The control will use the slower of this
parameter and the fan speed filter.
S162 BMS Backup Fan Setpoint
—Selects a temperature setpoint that will be activated in the
event of a BMS timeout. The BMS timer and S163 must be configured to “Backup Set” for this
parameter to be activated. This parameter is adjustable from 41-104°F (5-40°C). The default setting is
73°F (23°C)
S163 BMS Backup Fan Operation
—Sets the default operation for the fan speed control when a BMS
Timeout occurs. The options are: Disabled (default), BMS Backup Spd, Coupled and Backup Set.
Disabled: The fan will continue controlling to the last value written. This could be either the last
Fan Setpoint if controlling the fan off locally installed sensors or it could be the last value written
to Fanspeed STD when fan control is set to Manual.
BMS Backup Spd: Allows the user to program a fixed fan speed percentage setpoint. When the
BMS disconnect occurs, the fan speed will lock to this point. This setting is available when the fan
control sensor is set to Manual.
Coupled: Allows the fan speed to be controlled off the air temperature setpoint. The fan speed will
follow the call for cooling as described in 3.1.1 Unit/Fan Control.
Backup Set: Allows the user to program an alternate fan setpoint for the unit to use when a BMS
disconnect occurs. The setpoint is programmed on S163 Backup Fan Setpoint. When active, this
setpoint takes the place of S147 Fan Setpoint and is used to establish a new fan control band.
S164 Allow BMS to change Fanspeed
—Enables or disables BMS fan speed control. When this
parameter is disabled, the BMS will not have write access to this point. The fan control type must be
set to Manual before the value on this line can be changed to Yes.
S165 High Temp Limit Approach
—Sets the sensor to be used to increase the fanspeed value above
the fanspeed setpoint STD to the value set in the Analog Out high limit. This parameter is selectable
from Disabled, Supply and Return. The default is Return.
S166 High Temp Limit Approach At
—Sets the temperature differential below the high supply and
high return temperature limit where the fan speed would increase from fanspeed setpoint STD to
fanspeed MAX. This parameter is selectable from 0 - 10°F. The default is 2°F.
S16A FC / AirEco Ramp Up w/CFC
—Sets the selection to decouple the fan output from the call for
cooling. This parameter is selectable from No or Yes. The default is No.
S16B EC-Fan Mode
—Shows the status of the EC-Fan Mode. When the selection is shown as
full,
the
normal fanspeed control is being utilized. When the selection is shown as
light,
the fan control sensor
is forced to manual. This is used for the Liebert HPM
™
only.