Liebert DS Dimensions and Weights
24
Figure 19 Cabinet and floor planning dimensions—upflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton),
all compressor models
Table 16
Weights for upflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models
Compressor Type
Dry Weight, lb (kg) approximate
Model
053
070, 077
Semi-Hermetic Compressor
Water/Glycol
2650 (1205)
2800 (1270)
GLYCOOL/Dual-Cool 2830
(1287)
2980
(1352)
Scroll or Digital Scroll Compressor
Water/Glycol
2370 (1075)
GLYCOOL/Dual-Cool
2550 (1157)
DPN001167
Rev. 1
TOP VIEW
FRONT VIEW
High Volt Connection(s)
Alternate Condenser
Fluid Piping Entrance
Low Volt
Connection(s)
Shaded area indicates a
recommended minimum
clearance for component
access.
3/4"
(19mm)
Bezels
Condenser Cleanout Access
35"
(889mm)
33"
(838mm)
76"
(1930mm)
2"
(51mm)
109"
(2769mm)
108" (2743mm)
1-1/2"
(38mm)
24"
(610mm)
34"
(864mm)
Minimum required
for blower replacement
Required for
condenser cleanout
Note: Front air return unit shown. For rear
return unit, in addition to front service area
shown, also include 25" (635mm) on one
side of unit for access to rear return filter
box.
See DPN001196, Figure 30.
Summary of Contents for Liebert DS Series
Page 1: ......
Page 2: ......
Page 164: ...HVAC Maintenance Checklist 154 NOTES ...
Page 165: ...HVAC Maintenance Checklist 155 ...
Page 166: ...HVAC Maintenance Checklist 156 ...