Piping Schematics
116
Figure 89 Primary connection locations—upflow, air-cooled, 28-42kw (8-12 ton), semi-hermetic
compressor models
Point
Description
X
inches (mm)
Y
inches (mm)
Connection Size / Opening
inches (mm)
R1
Refrigerant Access (Top)
60-11/16 (1542)
1-7/8 (48)
22-1/2 x 15-3/16 (572 x 386)
R2
Refrigerant Access (Bottom)
63 (1600)
13-13/16 (351)
16-7/16 x 4 (418 x 102)
L1
Liquid Line System 1
79-3/16 (2011)
16-3/4 (425)
1/2 Cu Sweat
L2
Liquid Line System 2
76-1/2 (1943)
16-3/4 (425)
1/2 Cu Sweat
G1
Hot Gas Discharge 1
73-7/8 (1876)
16-3/4 (425)
5/8 Cu Sweat
G2
Hot Gas Discharge 2
70-1/8 (1780)
16-3/4 (425)
5/8 Cu Sweat
R3
Refrigerant Access (Side)
-
-
6 x 17-3/16 (152 x 437)
CGD*
Condensate Gravity Drain
-
-
3/4 FPT
CPD
Condensate Pump Discharge (Opt)
56-1/4 (1429)
11-1/8 (283)
1/2 Cu Sweat
HUM
Humidifier Supply Line
56-1/4 (1429)
9-1/8 (233)
1/4 Cu Sweat
ECS**
Econ-O-Coil Supply
56 (1423)
7-5/16 (186)
1-5/8 Cu Sweat
ECR**
Econ-O-Coil Return
56 (1423)
4-1/2 (114)
1-5/8 Cu Sweat
E1
Electrical Connection (High Voltage)
52-3/8 (1330)
30 (762)
2-1/2
E2
Electrical Connection (High Voltage)
46-7/8 (1191)
30 (762)
2-1/2
LV1
Electrical Connection (Low Voltage)
19-1/2 (495)
29-1/16 (738)
7/8
LV2
Electrical Connection (Low Voltage)
19-1/2 (495)
30-1/2 (775)
7/8
LV3
Electrical Connection (Low Voltage)
19-1/2 (495)
31-15/16 (811)
7/8
* Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
** Supplied on Dual-Cool systems only (4-pipe system)
All dimensions from
rear corner of unit
including panels
Blower
Outlet
22-1/2"
(572mm)
NOTES:
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is ± 1/2" (13mm).
Field-routed alternatives for refrigerant
gas and liquid line connection points.
See submittal page DPN001120 for
blower outlet and deck dimensional data.
16-7/16"
(418mm)
4"
(102mm)
35"
(889mm)
15-3/16"
(386mm)
86" (2184mm)
Top View
Front of Unit
20-1/16"
(509mm)
Factory Location
Front Section View
(Left Front Panel Not Shown)
14-1/4"
(362mm)
6"
(152mm)
17-3/16"
(437mm)
3-7/8"
(98mm)
15-7/8"
(403mm)
Left Side Section View
DPN001114