Maintenance
136
NOTICE
Risk of improper installation. Can cause equipment damage.
Only a properly trained and qualified technician should install or open this motor.
Use 60/75°C copper wire only. Use Class 1 wires only.
13.4
Humidifier—Infrared
During normal humidifier operation, deposits of mineral solids will collect in humidifier pan and on
the float switch. These must be cleaned periodically to ensure proper operation. Frequency of cleaning
must be locally established since it is dependant on humidifier usage and local water quality. A spare
pan is recommended to reduce maintenance time at unit. The Liebert autoflush system can greatly
increase the time between cleanings, but does not eliminate the need for periodic checks and
maintenance (see Liebert iCOM user manual SL-18835 for autoflush setup). To help reduce excessive
scaling in locations with difficult water quality, the use of Vapure is recommended (contact your local
Emerson representative).
13.4.1 Cleaning Humidifier Pan and Float Switch
Before turning off unit:
1. With unit operating, remove call for humidification at the Liebert iCOM control.
2. Let the blower operate 5 minutes to allow the humidifier and water to cool.
3. If unit has a condensate pump, turn unit OFF at Liebert iCOM control.
4. Pull out the humidifier standpipe in pan.
5. Inspect the O-ring (replace if necessary).
6. Let the pan drain and condensate pump operate (if applicable).
7. Disconnect power from the unit.
8. Disconnect the drain coupling from the bottom of the pan.
9. Remove the thermostat from the bottom of the pan and the retaining screws from the sides of the
pan.
10. Slide the pan out.
11. Loosen scale on side and bottom of pan with a stiff nylon brush or plastic scraper.
12. Flush with water.
13. Carefully clean scale off float switch (make sure to reinstall correctly (see
Figure 100
).
14. Reinstall the pan, thermostat, standpipe, drain coupling and screws into the humidifier.
15. Operate the humidifier and check for leaks.
!
WARNING
Risk of electric shock. Can cause injury or death.
Dangerous external voltages can be present at main fan terminal KL2 even after the motor
has been turned off.
!
WARNING
Risk of improper handling. Can cause injury.
Use proper skin protection when touching the electronics housing or allow time for the
housing to cool before replacing parts.
The electronics housing can get hot and can cause severe burns
!
CAUTION
Risk of improper moving, lifting and handling. Can cause equipment damage or injury.
Only properly trained and qualified personnel should work on this equipment. Fan modules
weigh in excess of 100lb. (45kg) each. Take precautions to avoid back injury and dropping
during removal.