Piping
93
Lee-Temp Receiver Refrigerant Level
On each receiver at the condenser are two refrigerant-level sight glasses. Refrigerant level will vary
with outside temperature. Check refrigerant level after the unit has been on for at least 15 minutes.
Sight Glass Levels
40°F (4.5°C) and lower—bottom sight glass is 3/4 full
40 to 60°F (4.5 to 15.5°C)—bottom sight glass is full
60°F (15.5°C) and higher—top sight glass is 3/4 full.
9.3.3
Water/Glycol Cooled System
The water/glycol cooled system is factory-charged and includes and includes a Paradenser condenser
and control valves.
Table 56
Water/Glycol-cooled and GLYCOOL suction pressure transducer settings
Function
R-22
R-407C
Gauge (Sea Level)
psiG (kPa)
Absolute
psiA (kPa)
Gauge (Sea Level)
psiG (kPa)
Absolute
psiA (kPa)
Pump-Down Cutout
35 (241)
50 (344)
35 (241)
50 (344)
Pump-Down Reset
65 (448)
80 (552)
65 (448)
80 (552)
Minimum to Start-Cooling
50 (345)
65 (448)
50 (345)
65 (448)
Low-Pressure Cutout (DX only)
20 (138)
35 (241)
20 (138)
35 (241)
Freeze Protection (DX w/Econ-O-Coil)
48 (331)
63 (434)
52 (358)
67 (461)
Due to control processing time, the pumpdown pressure at compressor shut off will be approximately
20 psiG (138 kPa) / 35 psiA (241 kPa) even though the set point is 35 psiG (241 kPa) / 50 psiA (344kPa).