Disassembling the Liebert DS for Transport
55
Figure 43 Component dimensions—downflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor
models
Table 29
Component weights—downflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic
Dry Weight, Approximate, Including Panels, lb (kg)
Component
Air-Cooled
Dual-Cool
Compressor Assembly
800 (364)
800 (364)
Filter & Electric Box Assembly
210 (96)
210 (96)
Blower & Coil Assembly
770 (350)
920 (418)
59" (1499mm)
DPN000801
Rev. 1
33"
(838mm)
76"
(1930mm)
26"
(660mm)
85" (2159mm)
Assembled Length
76"
(1930mm)
Assembled
Height
60-3/16"
(1529mm)
37"
(940mm)
39"
(991mm)
Compressor Assembly
Filter & Electric
Box Assembly
Blower & Coil
Assembly
Drawing views are simplified
with panels removed to show
overall dimensions.
See disassembly and handling
instructions in installation manual.