Piping Schematics
115
Figure 88 Primary connection locations downflow water/glycol/GLYCOOL 105kW (30 tons) all compressor
models, with EC fan
Point
Description
X
in. (mm)
Y
in. (mm)
Connection Size / Opening
in. (mm)
W
Water/Glycol/GLYCOOL Access
125-15/16 (3199)
9 (229)
3-1/2 (89) X 8" (203)
WS
Water/Glycol/GLYCOOL Supply
127-7/8 (3248)
10-1/16 (256)
2-1/8 Cu Sweat
WR
Water/Glycol/GLYCOOL Return
127-7/8 (3248)
13-1/4 (337)
2-1/8 Cu Sweat
CD
Condensate Drain (Infrared
Humidifier or No Humidifier)*
87-3/8 (2220)
31 (787)
3/4 FPT"
W/Optional Pump
83-13/16 (2129) "
30 (762)
1/2 Cu Sweat
HUM Humidifier Supply Line
85-5/16 (2167)
32-1/2 (825)
1/4" Cu Sweat
ECS
Econ-O-Coil Supply
101-7/8 (2588)
29 (737)
2-5/8" Cu Sweat
ECR
Econ-O-Coil Return
94-9/16 (2402)
29 (737)
2-5/8" Cu Sweat
HS
Hot Water Reheat Supply
CONSULT FACTORY
HR
Hot Water Reheat Return
CONSULT FACTORY
E1
Electrical Conn. (High Volt)
98-1/8 (2492)
31 (788)
2-1/2"
E2
Electrical Conn. (High Volt)
91 (2311)
31 (788)
2-1/2"
LV1
Electrical Conn. (Low Volt)
2 (51)
29 (737)
7/8"
LV2
Electrical Conn. (Low Volt)
2 (51)
30-7/8 (784)
7/8"
LV3
Electrical Conn. (Low Volt)
2 (51)
32 (813)
7/8"
B1
Blower Outlet
4-1/2 (114)
33 (838)
77-3/8 x 30 (1965 x 762)
*
Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
** Supplied on Dual Cooling systems only (4 piping system).
A
Note: Drawing not to scale.
Tolerance on all piping
dimensions is ± 1/2" (13mm).
FRONT VIEW
FRONT OF UNIT
SECTION A-A
BLOWER
OUTLET
All dimensions from
rear corner of unit
including panels
ECS
ECR
E1
E2
HUM
35"
(889mm)
132" (3353mm)
8" (203mm)
3-1/2"
(89mm)
W
WS
WR
CD
B1
LV1
LV2
LV3
O
X
Y
A
DPN002153
Rev. 0