Liebert DS Dimensions and Weights
29
Figure 24 Floor stand and floor planning dimension, downflow 53-77kW (15-22 tons) models with EC fans
Table 21
Floor stand and floor planning dimensions—downflow, 53-77kW (15-22 ton) models with EC
fans
Height, Dimension C
in. (mm)
24 (610)
30 (762)
36 (914)
42 (1067)
48 (1219)
B
C*
A
NOTES:
1) This floor stand should be used when EC fans are intended to be
lowered under a raised floo r. The standard Liebert DS floor stand
can be used if the fans are to remain in their original, raised position.
2) Right side of paneled unit is flush with right side of floor stand. All other
paneled sides overhang floor stand 1" (25mm).
3) The floor stand used with EC units is not symmetrical, and its
orientation to the Liebert DS is critical for lowering the EC fans.
Unless the floor stand is installed in the correct position, the blowers
will not lower into the floor stand.
4) Jack and jack support are shipped loose and are intended to be placed into position
under each fan and used to lower or raise that fan as needed.
*Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height “C.”
DPN002151
REV 0
Piping access area
See Note 4
32" (813mm)
Center Feet
95-1/2" (2426mm)
Support Feet Centers
3/4"
(19mm)
3/4"
(19mm)
3/4"
(19mm)
62-3/4" (1594mm)
31-1/2"
(800mm)
1"
(25mm)
33"
(838mm)
35" (889mm)
Overall Depth
97" (2464mm)
7/8"
(23mm)
3" (76mm)
98-1/2" (2502mm)