61
Figure 49 Component dimensions—downflow, air-cooled, 105kW (30 ton), semi-hermetic compressor
models; forward-curved and EC fan
Table 35
Component weights—downflow, air-cooled, 105kW (30 ton), semi-hermetic compressors;
forward-curved and EC fan
Component
Dry Weight, lb (kg) Approximate (Includes Panels)
Forward Curved Fans
EC Fans
Air-Cooled
Dual Cool
Air-Cooled
Dual Cool
Compressor Assembly
950 (432)
950 (432)
950 (432)
950 (432)
Filter & Electric Box Assembly
270 (123)
270 (123)
270 (123)
270 (123)
Blower & Coil Assembly
1820 (827)
2180 (991)
1560 (708)
1915 (870)
37"
(940mm)
59-7/16"
(1510mm)
DPN001057
Rev. 1
131" (3327mm)
Assembled Length
33"
(838mm)
26"
(660mm)
105" (2667mm)
76"
(1930mm)
76"
(1930mm)
Assembled
Height
39"
(991mm)
41-11/16"
(1059mm)
Filter and Electric Box Assembly
Compressor Assembly
Blower and Coil Assembly
Drawing views are simplified
with panels removed to show
overall dimensions.
See disassembly and handling
instructions in installation manual.