32 Chapter 4 Operator Control And Display Panel
Liebert APM 90 Integrated Modular UPS User Manual
Menu
Item
Explanation
Communication mode
Set the communication mode
Callback times
If the communication mode of the Intellislot 1 port is modem mode,
this parameter sets the number of times of a number is redialed to
send an alarm notification
Phone No.1
If the communication mode of the Intellislot 1 port is modem mode,
this is the first phone number to be dialed (to send an alarm
notification)
Phone No.2
If the communication mode of the Intellislot 1 port is modem mode,
this is the second phone number to be dialed (to send an alarm
notification)
Phone No.3
If the communication mode of the Intellislot 1 port is modem mode,
this is the third phone number to be dialed (to send an alarm
notification)
Command password
Sets the control password. Set by commissioning engineer
Settings
Protocol
Sets the communication protocol: Velocity, YDN23. However,
because no optional communication cards of the UPS support
Velocity, users can only select YDN23
Battery maintenance test
This test performs a partial discharge of the battery to obtain a rough
estimate of the battery capacity. Load must be between 20% and 100%
Battery capacity test
This test performs a full discharge of the battery to obtain a precise
measure of the battery capacity. Load must be between 20% and 100%
System test
This is a self-test of the UPS. When the user activates this function, a
window appears about five seconds later to show the test result
Stop testing
Manually stops a battery maintenance test, battery capacity test or
system test
Freshening charge
Manually initiates a battery freshening charge
Command
(initiate, stop
battery, system
test or
freshening
charge; control
password
required)
Stop freshening charge
Manually stops a battery freshening charge
Monitor Version
Provides the monitoring software version
Rectifier Version
Provides the rectifier software version
Inverter Version
Provides the inverter software version
Bypass Version
Provides the bypass software version
Version
SPM Version
Provides the SPM DSP software version
Keypad window
The functions of the menu keys F1
~
F5 for the current screen are shown by self-explanatory icons on the
keypad window as appropriate.
4.4
Prompt Window
A prompt window is displayed during the operation of the system to alert you to certain conditions or to
require your confirmation of a command. The prompts are provided in Table 4-8.
Table 4-8
Prompts and meanings
Prompt
Meaning
Transfer with interrupt, confirm or
cancel
The inverter and bypass supplies are not synchronized and any load transfer
between the inverters and bypass will cause a brief load interruption
The load is too high to be transferred
with interrupt
The total load must be less than the capacity of one UPS to allow a parallel
system to perform an interrupted transfer from bypass to inverter
This operation leads to output
shutdown, confirm or cancel
The bypass is abnormal, turning off the inverters will cause the load to be
de-energised