Section 4: Orifice plate installation and removal instructions
3-9008-001 Rev M
January 2015
“Extended time” procedure
79
13.
Monitor the fluid/gas pressure in the Top (14) until it is equal to ambient conditions.
14.
Loosen each Clamping Bar Screw (11) located on the Clamping Bar (12 or 12HP)
approximately two turns with the Operating Wrench (2).
Step 14
Step 15
RELEASE OF FLUIDS OR COMPONENTS HAZARD
The Clamping Bar (12 or 12HP) may not be securely in place. Sudden release of fluid or internal
components may occur. Never place the Operating Wrench (2) on the Slide Valve Shaft (5), or
any body part in front of the top opening in the Top (14).
Failure to do so may cause serious injury or death.