SERVICE MANUAL Blast Chiller Freezer 100 - 200
4.3.17 Probe’s
4.3.17.1 Functionality
Every cable has printed the name
of component ( cell/evap/outevap)
4.3.17.2 Probe functions
Descriptions Colours Where are positioned
Functionality
Cavity probe
Blue
Inside of the cavity on upper
fan
Control logic the cavity temperature
Evaporator probe Grey
Inside of evaporator
Control logic the defrost limit temperature
Out evaporator
Green
Out side, togheter sensor to
thermostatich valve
Control logic the start stop cavity fan (+20 it is
stopped togheter the logic control of the evapo-
rator probe) + Usa model control the by pass of
the solenoid valve ( -10°C elv2) up to this tem-
perature it is remain closed
Condenser probe Black
Cooling unit in the outpipe of
condenser
Control logic higt temperature of the condenser