Anomaly
Type of
anomaly
Description
Possible causes
Instructions
to User
Service Action
(phase# refers to
Service Manual)
T
he compressor oscillates intermit-
tently
Suction service valve closed
Discharge service valve
closed
Refrigerant load insufficient
Wrong operation of the low
pressure switch
Condenser insufficient or dirty
Air in the circuit
Intervention motor protection
Call service
Open the service valve
Add gas
Check the setting and the assembly of the low
pressure switch
Check the flow rate of air or water to the conden-
ser. Clean the condenser
Make a total vacuum
Check that the quantity of refrigerant is sufficient.
Check electrical connections
The compressor oscillates continu-
ously
Defective pressure switches
Refrigerant load and dis-
charge pressure too high
Blocked dehydrators filters
Call service
Repair or replace
Remove excess refrigerant
Replace filters
Decrease in compressor efficiency
Leakages from the valves or
dirty valve plate; breakage of
valves
Leakage from internal safety
valve
Leakage from the gasket of
the head
Piston rings wear
Call service
Disassemble the heads and check the valve plate
and the valves
Replace the safety valve
Replace the gasket
Replace the compressor
Leakage from the gasket of the
head
Heads bolts not enough
tighten
Call service
Replace the gasket and tighten bolts again
Presence of liquid in the carter
Piping not properly designed
The defrost cycle does not
work correctly
Wrong calibration of the ex-
pansion valve
The evaporator does not work
Call service
Correct piping
Check the defrost cycle
Replace the valve or change the calibration
Check the evaporator condition
High pressure too low
The discharge valve are not
gastight
Crankcase heater does not
work
The piston rings are worn
Call service
Disassemble the heads and check the valve plate
and the valves
Replace the heater
Replace the compressor
Low suction pressure
Quantity of refrigerant insuffi-
cient
Problems with evaporator fans
Dehydrators filters dirty
Call service
Add gas
Check
Replace filters