3. Click OK.
To configure a Limit:
Double-click on the field to set the following values:
Above and Below Setpoint: % of Full Scale (the point at which the reading goes
out of limit)
Examples:
100% of 120V Full Scale = 120V
90% of 120V Full Scale = 108V
Above and Below Return Hysteresis: the point at which the reading goes back
within limit (see figure below)
Examples:
Above Setpoint = 110%; Below Setpoint = 90%
(Out of Limit above 132V);(Out of Limit below 108V)
Above Return Hysteresis = 105%; Below Return Hysteresis = 95%
(Stay out of Limit until below 126V)(Stay out of Limit until above 114V)
Primary Fields: These fields are display only. They show what the setpoint and
return hysteresis value are for each limit.
TIME
Above Limit
condition
Below Limit
condition
Above Limit Trigger point
Return point from Above Limit condition
Below Limit Trigger point
Return point from Below Limit condition
HYSTERESIS
HYSTERESIS
-
MEASURED VALUE
(if applicable)
+
MEASURED VALUE
0