B: Modbus Map and Retrieving Logs
Doc# E149721 MM-3
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description (Note 1)
Format
Range (Note 6)
Units or Resolution
Comments
# Reg
Modbus Address
Hex
Decimal
read-only
05DB
-
05DC
1500 -
1501 W-hours, Received
SINT32
0 to 99999999 or
0 to -99999999
Wh per energy format
2
05DD
-
05DE
1502 -
1503 W-hours, Delivered
SINT32
0 to 99999999 or
0 to -99999999
Wh per energy format
2
05DF
-
05E0
1504 -
1505 W-hours, Net
SINT32
-99999999 to 99999999
Wh per energy format
2
05E1
-
05E2
1506 -
1507 W-hours, Total
SINT32
0 to 99999999
Wh per energy format
2
05E3
-
05E4
1508 -
1509 VAR-hours, Positive
SINT32
0 to 99999999
VARh per energy format
2
05E5
-
05E6
1510 -
1511 VAR-hours, Negative
SINT32
0 to -99999999
VARh per energy format
2
05E7
-
05E8
1512 -
1513 VAR-hours, Net
SINT32
-99999999 to 99999999
VARh per energy format
2
05E9
-
05EA
1514 -
1515 VAR-hours, Total
SINT32
0 to 99999999
VARh per energy format
2
05EB
-
05EC
1516 -
1517 VA-hours, Total
SINT32
0 to 99999999
VAh per energy format
2
05ED
-
05EE
1518 -
1519 W-hours, Received, Phase A
SINT32
0 to 99999999 or
0 to -99999999
Wh per energy format
2
05EF
-
05F0
1520 -
1521 W-hours, Received, Phase B
SINT32
0 to 99999999 or
0 to -99999999
Wh per energy format
2
05F1
-
05F2
1522 -
1523 W-hours, Received, Phase C
SINT32
0 to 99999999 or
0 to -99999999
Wh per energy format
2
05F3
-
05F4
1524 -
1525 W-hours, Delivered, Phase A
SINT32
0 to 99999999 or
0 to -99999999
Wh per energy format
2
05F5
-
05F6
1526 -
1527 W-hours, Delivered, Phase B
SINT32
0 to 99999999 or
0 to -99999999
Wh per energy format
2
05F7
-
05F8
1528 -
1529 W-hours, Delivered, Phase C
SINT32
0 to 99999999 or
0 to -99999999
Wh per energy format
2
05F9
-
05FA
1530 -
1531 W-hours, Net, Phase A
SINT32
-99999999 to 99999999
Wh per energy format
2
05FB
-
05FC
1532 -
1533 W-hours, Net, Phase B
SINT32
-99999999 to 99999999
Wh per energy format
2
05FD
-
05FE
1534 -
1535 W-hours, Net, Phase C
SINT32
-99999999 to 99999999
Wh per energy format
2
05FF
-
0600
1536 -
1537 W-hours, Total, Phase A
SINT32
0 to 99999999
Wh per energy format
2
0601
-
0602
1538 -
1539 W-hours, Total, Phase B
SINT32
0 to 99999999
Wh per energy format
2
0603
-
0604
1540 -
1541 W-hours, Total, Phase C
SINT32
0 to 99999999
Wh per energy format
2
0605
-
0606
1542 -
1543 VAR-hours, Positive, Phase A
SINT32
0 to 99999999
VARh per energy format
2
0607
-
0608
1544 -
1545 VAR-hours, Positive, Phase B
SINT32
0 to 99999999
VARh per energy format
2
0609
-
060A
1546 -
1547 VAR-hours, Positive, Phase C
SINT32
0 to 99999999
VARh per energy format
2
060B
-
060C
1548 -
1549 VAR-hours, Negative, Phase A
SINT32
0 to -99999999
VARh per energy format
2
060D
-
060E
1550 -
1551 VAR-hours, Negative, Phase B
SINT32
0 to -99999999
VARh per energy format
2
060F
-
0610
1552 -
1553 VAR-hours, Negative, Phase C
SINT32
0 to -99999999
VARh per energy format
2
0611
-
0612
1554 -
1555 VAR-hours, Net, Phase A
SINT32
-99999999 to 99999999
VARh per energy format
2
0613
-
0614
1556 -
1557 VAR-hours, Net, Phase B
SINT32
-99999999 to 99999999
VARh per energy format
2
0615
-
0616
1558 -
1559 VAR-hours, Net, Phase C
SINT32
-99999999 to 99999999
VARh per energy format
2
0617
-
0618
1560 -
1561 VAR-hours, Total, Phase A
SINT32
0 to 99999999
VARh per energy format
2
0619
-
061A
1562 -
1563 VAR-hours, Total, Phase B
SINT32
0 to 99999999
VARh per energy format
2
061B
-
061C
1564 -
1565 VAR-hours, Total, Phase C
SINT32
0 to 99999999
VARh per energy format
2
061D
-
061E
1566 -
1567 VA-hours, Phase A
SINT32
0 to 99999999
VAh per energy format
2
061F
-
0620
1568 -
1569 VA-hours, Phase B
SINT32
0 to 99999999
VAh per energy format
2
0621
-
0622
1570 -
1571 VA-hours, Phase C
SINT32
0 to 99999999
VAh per energy format
2
0623
-
0624
1572 -
1573 W-hours, Received, rollover count
UINT32
0 to 4,294,967,294
0625
-
0626
1574 -
1575 W-hours, Delivered, rollover count
UINT32
0 to 4,294,967,294
0627
-
0628
1576 -
1577 VAR-hours, Positive, rollover count
UINT32
0 to 4,294,967,294
0629
-
062A
1578 -
1579 VAR-hours, Negative, rollover count
UINT32
0 to 4,294,967,294
062B
-
062C
1580 -
1581 VA-hours, rollover count
UINT32
0 to 4,294,967,294
Primary Energy Block
* Wh received & delivered always have opposite signs
* Wh received is positive for "view as load", delivered is
positive for "view as generator"
* 5 to 8 digits
* decimal point implied, per energy format
* resolution of digit before decimal point = units, kilo, or
mega, per energy format
* see note 10
These registers count the number of times their
corresponding energy accumulators have wrapped from
+max to 0. They are reset when energy is reset.