![Electro Industries Shark 200S Installation & Operator'S Manual Download Page 166](http://html.mh-extra.com/html/electro-industries/shark-200s/shark-200s_installation-and-operators-manual_2379717166.webp)
Doc
#
E149721
B - 30
B: Modbus Map and Retrieving Logs
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Param 1-4: These are defined for each event (see following table).
NOTE
: The System Log Record is 20 bytes, consisting of the Record Header (12
bytes) and Payload (8 bytes). The Timestamp (6 bytes) is in the header. Typically,
software will retrieve only the timestamp and payload, yielding a 14-byte record. The
table below shows all defined payloads.
Group
(Event
group)
Event
(Event
within
group)
Mod
(Event
modifier)
Channel
(1-2 for
COMs, 7
for USER,
0 for FW)
Parm1
Parm2
Parm3
Parm4
Comments
0
Startup
0
0
0
FW version
Meter Run
Firmware
Startup
1
Log Activity
1
log#
1-4
0xFF
0xFF
0xFF
0xFF
Reset
2
log#
1-4
0xFF
0xFF
0xFF
0xFF
Log Retrieval
Begin
3
log#
0-4
0xFF
0xFF
0xFF
0xFF
Log Retrieval
End
2
Clock Activity
1
0
1-4
0xFF
0xFF
0xFF
0xFF
Clock Changed
2
0
0
0xFF
0xFF
0xFF
0xFF
Daylight Time
On
3
0
0
0xFF
0xFF
0xFF
0xFF
Daylight Time
Off
4
sync
method
0
0xFF
0xFF
0xFF
0xFF
Auto Clock
Sync Failed
5
sync
method
0
0xFF
0xFF
0xFF
0xFF
Auto Clock
Sync Resumed
3
System Resets
1
0
0-4, 7
0xFF
0xFF
0xFF
0xFF
Max & Min
Reset
2
0
0-4, 7
0xFF
0xFF
0xFF
0xFF
Energy Reset
3
slot#
0-4
1
(inputs)
or 2
(outputs)
0xFF
0xFF
0xFF
Accumulators
Reset
Summary of Contents for Shark 200S
Page 1: ...S h a r k 200S ...