![Electro Industries Shark 200S Installation & Operator'S Manual Download Page 43](http://html.mh-extra.com/html/electro-industries/shark-200s/shark-200s_installation-and-operators-manual_2379717043.webp)
Doc
#
E149721
2 - 11
2: Meter Overview and Specifications
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
1
For 2.5 element programmed units, degrade accuracy by an additional 0.5% of
reading.
• For 1A (Class 2) Nominal, degrade accuracy by an additional 0.5% of reading.
• For 1A (Class 2) Nominal, the input current range for Accuracy specification is
20% of the values listed in the table.
2
For unbalanced voltage inputs where at least one crosses the 150V auto-scale
threshold (for example, 120V/120V/208V system), degrade accuracy by additional
0.4%.
Power Factor
0.2% of reading
1,2
(0.15 to 5)A @ (69 to 480)V
@ +/- (0.5 to 1) lag/lead PF
Frequency
+/- 0.001Hz
(45 to 65)Hz
Load Bar
+/- 1 segment
1
(0.005 to 6)A
Summary of Contents for Shark 200S
Page 1: ...S h a r k 200S ...