Measurement Methods
Voltage, Current:
True RMS
Power:
Sampling at 400+ Samples per
Cycle on All Channels Measured
Readings Simultaneously
A/D Conversion:
6 Simultaneous 24 bit Analog to
Digital Converters
Update Rate
Watts, VAR and VA:
Every 6 cycles, e.g., 100
milliseconds (Ten times per
second) @60Hz
All other parameters:
Every 60 cycles, e.g, 1 second
@60Hz
Communication Format
1. RS485
2. IrDA Port through Face Plate
Protocols:
Modbus RTU, Modbus ASCII, DNP
3.0, Modbus TCP (for Ethernet-
enabled)
Com Port Baud Rate:
RS485 Only: 1200, 2400, 4800*;
All Com Ports: 9600 to 57600 bps
Com Port Address:
001-247
Data Format:
8 Bit, No Parity (RS485: also Even
or Odd Parity*)
*With Runtime Firmware Version 26 or higher
Wireless Ethernet (Optional)
802.11b Wireless or
WiFi or RJ45 Connection
10/100BaseT Ethernet
Wireless Security
64 or 128 bit WEP; WPA; or WPA2
Modbus TCP Protocol