![Electro Industries Shark 200S Installation & Operator'S Manual Download Page 165](http://html.mh-extra.com/html/electro-industries/shark-200s/shark-200s_installation-and-operators-manual_2379717165.webp)
Doc
#
E149721
B - 29
B: Modbus Map and Retrieving Logs
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
B.5.5: Log Record Interpretation
The records of each log are composed of a 6 byte timestamp, and N data. The content
of the data portion depends on the log.
System Event Record:
Size
: 14 bytes (20 bytes image).
Data
: The System Event data is 8 bytes; each byte is an enumerated value.
• Group: Group of the event.
• Event: Event within a group.
• Modifier: Additional information about the event, such as number of sectors or log
number.
• Channel: The port of the Shark® 200S meter that caused the event.
0
Firmware
1
COM 1 (IrDA)
2
COM 2 (RS485)
7
User (Face Plate)
Byte
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Value
timestamp
Group
Event
Mod
Chan
Param1
Param2
Param3
Param4