• # Registers: The number of registers to log in the record. The size of the record in
memory is [12 + (# Registers x 2)]. The size during normal log retrieval is [6 + (#
Registers x 2)]. If this value is 0, the log is disabled. Valid values are {0-117}.
• # Sectors: The number of Flash Sectors allocated to this log. Each sector is 64kb,
minus a sector header of 20 bytes. 15 sectors are available for allocation between
Historical Logs 1, 2, and 3. The sum of all Historical Logs may be less than 15. If
this value is 0, the log is disabled. Valid values are {0-15}.
• Interval: The interval at which the Historical Log's Records are captured. This value
is an enumeration:
0x01
1 minute
0x02
3 minute
0x04
5 minute
0x08
10 minute
0x10
15 minute
0x20
30 minute
0x40
60 minute
Register List:
Registers:
0x7919 - 0x798D
Size:
1 register per list item, 117 list items
The Register List controls what Modbus Registers are recorded in each record of the
Historical Log. Since many items, such as Voltage, Energy, etc., take up more than 1
register, multiple registers need to be listed to record those items.
For example: Registers 0x03E7 and 0x03E8 are programmed to be recorded by the
historical log. These registers program the log to record "Primary Readings Volts A-N."
• Each unused register item should be set to 0x0000 or 0xFFFF to indicate that it
should be ignored.