• sector# values: 0-63
• slot# values: 1-2
NOTES
:
• The clock changed event shows the clock value just before the change in the Mod
and Parm bytes. Parms are bit-mapped:
• b31 - b28
month
• b27 - b23
day
• b22
daylight savings time flag
• b20 - b16
hour
• b13 - b8
minute
• b5 - b0
second
• unused bits are always 0
• Sync method: 1 = NTP.
• Stimulus for a flash sector error indicates what the flash was doing when the error
occurred: 1 = acquire sector, 2 = startup, 3 = empty sector, 4 = release sector, 5 =
write data.
• Flash error counters are reset to zero in the unlikely event that both copies in
EEPROM are corrupted.
• The flash job queue is flushed (and log records are lost) in the unlikely event that
the queue runs out of space.
• A "babbling log" is one that is saving records faster than the meter can handle long
term. When babbling is detected, the log is frozen and no records are appended
until babbling ceases. For as long as babbling persists, a summary of records
discarded is logged every 60 minutes. Normal logging resumes when there have
been no new append attempts for 30 seconds. Onset of babbling occurs when a log
fills a flash sector in less than an hour (applies only to Alarm, I/O Change, Histori-
Summary of Contents for Shark 200S