ELECTRO FREEZE Soft Serve Model 99T-RMT
PROBLEM
PROBABLE CAUSE
REMEDY
12.1 Compressor/Condensing Circuit Troubleshooting Tables
1.
Improperly wired.
1.
Contact your Electro Freeze Distributor
for service.
2.
Low line voltage.
2.
Ask power company to increase voltage
to not less than 10% below dataplate
rating or have transformer installed.
Have wire checked for inadequate wire
size.
3.
Open start capacitor. (Single phase
only)
3.
Contact your Electro Freeze Distributor
for service.
4.
High discharge pressure.
4.
See "Discharge pressure too high" this
section.
Compressor
will not start –
hums
intermittently
(cycling on
overload)
5.
Defective compressor
5.
Contact your Electro Freeze Distributor
for service.
1.
Low line voltage.
1.
Ask power company to increase voltage
to not less than 10% below nameplate
rating or install transformer.
2.
Improperly wired.
2.
Contact your Electro Freeze Distributor
for service.
4.
Running capacitor shorted. (Single
phase only).
4.
Contact your Electro Freeze Distributor
for service.
Compressor
starts, but pulls
high amps.
5.
Start capacitor weak. (Single phase
only).
5.
Contact your Electro Freeze Distributor
for service.