KGL Operating Manual – VS 3010 BS
2018-07-02
/
19 178
1.
2.
3.
4.
5.
6.
4 VS 3010 BS Function
4.1 Starting characteristics
The following are distinguished for any start-up of the controller:
First start
Restart
4.1.1 First start
The controller is reset to the factory settings during a first start.
The configuration of the controller
using the LDSWin
must be backed up before any first start
software! All variables in battery backed-up RAM are specifically set to 0 during any first start.
The first start is initiated in the following ways:
Predefined parameters are loaded by the controller when first switching on the system (i.e. after a first
start)
After a firmware update.
If the controller has established using an internal check that no correct parametrisation is available.
After the switching (adjustment) using the coding switches of the DIP switch S1:
Execution of a desired first start
The configuration of the controller
using the LDSWin software!
must be backed up before any first start
Put coding switch 2 of the DIP switch S1 in a different position:
For details, see chapter
.
VS 3010 BS Installation and start-up, page 84
Switch off controller for 5 seconds and then switch on again.
Put coding switch 2 of the DIP switch S1 back in the original position.
Switch off controller and switch on again.
Restore the configuration of the controller using the LDSWin software.
4.1.2 Restart
The restart is always performed after restore of the power supply if the parametrisation has been preserved.
All variables (except the parameters) of the fault memory and all archive data are deleted.