KGL Operating Manual – VS 3010 BS
2018-07-02
/
137 178
SETPOINTS ID: XXXXX
3 Compressor monitoring
Continue to menu 3-3
4 Refrigerant monitoring
Continue to menu 3-4
5 External alarm
Continue to menu 3-5
6 Base load
Continue to menu 3-6
7 Messages
Continue to menu 3-7
8 D2D *
Continue to menu 3-8
* Discharge gas defrosting only when this has also been activated, see chapter
Default settings with S1, page
.
Menu 3-1 System configuration
CONFIG ID:
XXXXX
Input
Default
Dim.
Sensor match
→
Calibration of the pressure transducers
→
Screen 3-
1-a
Kältem. Z1
XXXXX →
Selection of the refrigerant for the Z1 circuit
→
Screen 3-
1-b
-
Kältem. Z2
XXXXX →
Selection of the refrigerant for the Z2 circuit
→
Screen 3-
1-c
-
Oil eq. line X
Disable / enable oil equalisation YES/NO
Y/N
N
-
Boost./cascade
Activation of the booster / cascade operation
ON
/OFF
OFF
-
Kaskadenreg.
Activation of the cascade controller (in booster operation).
Parameter only visible if parameter "Boost./Cascade" = ON
ON
/OFF
OFF
-
Control type Z2
Select control type of the Z2 circuit
→
Screen 3-
1-d
-
Kn.Nr.Verbr.
CAN bus address (node number) of the case controller that controls booster / satellite compressor
(Z2 compressor consumer controller)
Only visible when Z2 control type = "via consumer".
1..99,
--
---
-
Suction gas
bypass
suction gas bypass YES/NO, see chapter
Compressor packs with suction gas bypass (evaporator
Y/N
N
-
Kn.Nr.Kaskade
Input of the CAN bus address of the LT consumer in the LT circuit.
Only visible if Z2 control type via "consumer" has been activated, see chapter
using a case controller, page 60
1..99,
--
---
-
Anz.Verd. Z1 X
Input of the number of Z1 compressors
1..4/8
4/8
-
AnzVerd.m.LS
Z1
Input of the number of compressors with capacity stages Z1
0..4
0
-
Anz L-Stufen Z1
X
Input of the number of capacity stages / compressors in Z1
1..3
1
-
Bypass inv. Z1
X
Inversion of the function of the valves for capacity control (bypass) in Z1
Y/N
N
-
Freig. Z1-Verd.
→
Display enabling compressor stages Z1
→
Screen 3-
1-e
-
Ver.m.LA.AUS.
Z1 X
For load shedding and capacity-controlled compressors in Z1: shut down compressor completely or
only shut down compressor capacity stage
Y/N
N
-
Mot.sch.Verd.Z1
X
Enable motor overload cutout YES/NO
Y/N
N
-
Motsch.sperr.Z1
Enable motor protection lock YES/NO
(only visible if Mot.cutout C. Y
Y/N
Y
-
Oil/HP fault Z1
X
Oil pressure difference switch / HP switch compressor YES/NO
Y/N
N
-