KGL Operating Manual – VS 3010 BS
2018-07-02
/
150 178
B. UNLO T ID: XXXXX
Input
Default
Dim.
B. unlo t. F1 XXX s
Only the available condenser capacity stages are displayed.
3..250
10
sec.
B.unlo t. F2 XXX s
3..250
20
sec.
...
B. unlo t. F8 XXX s
3..250
40
sec.
Base module: 1 – max. 4 capacity stages
with first SIOX extension module: 1 – max. 8 capacity stages
Screen 3-2-2-2-d Variable time for condenser capacity stages OFF
V. UNLO T ID: XXXXX
Input
Default
Dim.
V. UNLO T L1 XXX s
Only the available condenser capacity stages are displayed.
3..250
20
sec.
V. UNLO T L2 XXX s
3..250
40
sec.
...
V. UNLO T L8 XXX s
3..250
90
sec.
Base module: 1 – max. 4 capacity stages
with first SIOX extension module: 1 – max. 8 capacity stages
Menu 3-2-3 Cascade regulation
KASK-REG. ID: XXXXX
Input
Default
Dim.
tcZ2-Max XX°C
max. t -setpoint for setpoint shift Z2
c
-10..10
0
°C
tcZ2-Min XX°C
min. t -setpoint for setpoint shift Z2
c
-20..10
-10
°C
tcZ2-toZ1 Diff XXK
Offset for tc Z2 setpoint calculation
0..20
5
K
Soll-Rampe/m XXK
Speed setpoint ramp tcZ2
1..100
10
K
Setp. SH XXK
Superheat setpoint
0..20
8
K
Min.Überh. XXK
Minimum superheat
0..10
2
K
Tandembetr. XXX
Control of one or two expansion valves
↑, ↓, (Y/N)
Y
-
Enable C2 XX%
Threshold for enabling C2
20..70
35
%
Disable C2 XX%
Threshold for disabling C2
0..30
5
%
P-Wert TReg XX.XX
P-factor temperature regulation
0..99.99
4
-
I-Wert TReg XX.XX
I-factor temperature regulation
0..99.99
0.30
-
D-Wert TReg XX.XX
D-factor temperature regulation
0..99.99
5.00
-
Offset TReg XXX%
Offset for temperature regulation opening degree
0..100
10
%
P-Wert ÜHReg XX.XX
P-factor superheat regulation
0..99.99
5
-
P-Wert ÜHReg XX.XX
I-factor temperature regulation
0..99.99
0.10
-
P-Wert ÜHReg XX.XX
D-factor temperature regulation
0..99.99
5.00
-
Offset ÜHReg XX%
Offset for superheat regulation opening degree
0..100
10
%
emerg.c-o OD XX%
Maximum emergency opening degree
0..50
10
%
delay min SH XXXs
Delay for min. superheat
0..600
9
sec.
Setup time 1.0 min.
Start-up time of the regulation after restart
0..100.0
1.0
Min. Einspr.dauer XXm
Injection time of the regulation after restart
0.0..100.0
0.2
Min. Maximaler ÖG XXX%
Maximum permissible opening degree
20..100
100
%
corr.off to
Correction offset for pressure losses Z1
0..20
1
K