KGL Operating Manual – VS 3010 BS
2018-07-02
/
89 178
Coding switch 4 setting
DIP switch S1
Coding switch 4
Switch position
Discharge gas defrosting
ON
with discharge gas defrosting
OFF
without discharge gas defrosting
Coding switch 5 setting
DIP switch S1
Coding switch 5
Switch position
Service mode
ON
Service mode activated
OFF
Normal operating mode
After every power failure, the system starts in service mode with default parameters for service
purposes. Parameter changes are not saved permanently (power failure). DIP switch S1 coding
switch 5 may
be set to ON for service mode purposes.
only
It is
for the operation of the system that the
(DIP switch
strictly required
service mode is deactivated
S1 coding switch 5
be in the OFF position)!
must
Coding switches 6 and 7 setting - firmware update mode
DIP switch S1 coding switches 6 and 7 specify the operating mode of the firmware update mode:
DIP switch S1
Coding switches 6 and 7
Switch position
Firmware update
mode
ON
Normal operating mode
OFF
Firmware update mode,
for more details, see chapter
DIP switch S1 coding switches 6 and 7 may
be set to OFF for
only
purposes. In this state, the controller waits for a firmware update via a connected service PC. It is
strictly required for the operation of the system that the
is deactivated (DIP
firmware update mode
switch S1 coding switches 6 and 7
be in the ON position)! If a switch position is changed (DIP
must
switch S1, coding switch 2 or 3) after the start-up, the default parameters of the set system
configuration are loaded during the next start (power failure) of the controller and a first start is
performed.
After changing the switch positions of both S1 and S2 (address selector switch for CAN bus), the