KGL Operating Manual – VS 3010 BS
2018-07-02
/
141 178
LP-Control ID: XXXXX
2 Verdichtersteu.Z2
Continue to menu 3-2-1-2
3 to-adjustment Z1
Continue to menu 3-2-1-3
4 to-adjustment Z2
Continue to menu 3-2-1-4
5 LP control Day Z1
Continue to menu 3-2-1-5
6 LP control Night Z1
Continue to menu 3-2-1-6
7 LP control Day Z2
Continue to menu 3-2-1-7
8 LP control Night Z2
Continue to menu 3-2-1-8
Menu 3-2-1-1 Compressor control Z1
V.STEU Z1
ID: XXXXX
Input
Default
Dim.
Type of
control →
Selection list LP type of control Z1
→
Screen 3-2-1-
1-a
The following parameters are only visible if combined control has been selected as type of control
M.com.out.
reg.
Load Z1 fixed-speed compressor with bypass stages for combined control -stages, see chapter
unloading of fixed-speed compressors during operation with capacity-controlled compressors, page 27
Y/N
N
-
Min.
Drehz. xxx
%
Minimum speed of the FC Z1 compressor for combined control
0..15
0
%
P-factor xx.
x
P-factor of the compressor speed control Z1
0.0..
2.0
0.3
-
I-factor X.
XX
I-factor of the compressor speed control Z1
0.00..
1.00
0.5
-
Screen 3-2-1-1-a Type of control Z1
REG Z1 ID: XXXXX
Input
Default
Dim.
Step controller √
Selection list LP type of control
√
√
-
Combined control
Menu 3-2-1-2 Compressor control Z2
V.STEU Z2 ID:
XXXXX
Input
Default
Dim.
Type of control →
Selection list LP type of control Z2
→
Screen 3-2-1-2-a
The following parameters are only visible if combined control has been selected as type of control
M.com.out.reg.
Load Z2 fixed-speed compressor with bypass stages for combined control -stages, see
chapter
Y/N
-
Min. Drehz. xxx %
Minimum speed of the FC Z2 compressor for combined control
0..15
0
%
P-factor xx.x
P-factor of the compressor speed control Z2
0.0..2.0
0.3
-
I-factor X.XX
I-factor of the compressor speed control Z2
0.00..
1.00
0.5
-
Screen 3-2-1-2-a Type of control Z2
REG Z2 ID: XXXXX
Input
Default
Dim.
Step controller √
Selection list LP type of control
√
√
-
Combined control
Menu 3-2-1-3 t -adjustment Z1
0