KGL Operating Manual – VS 3010 BS
2018-07-02
/
151 178
KASK-REG. ID: XXXXX
Input
Default
Dim.
Manual mode
Manual entry of the opening degree
---, 0..100
---
%
Menu 3-3 Compressor monitoring
COMP MON ID:
XXXXX
Input
Default
Dim.
Comp. OFF temp
XXX °C
Disable compressor if temperature too high
80..
145
130
°C
Comp. ON temp
XXX °C
Enable compressor after temperature too high
50..
120
100
°C
Comp temp del. XX
m
Delay time for message
Cyl.temp.Z1/Z2 Cx
0..5
3
Min.
to Comp OFF Z1
XXX °C
tc-limit value for disable of
Z1 compressor capacity stages
20..
71
52
°C
to Comp ON Z1
XXX °C
tc-limit value for enable of
Z1 compressor capacity stages
15..
65
45
°C
HP EMERG.-OFF
Z1
The EMERGENCY OFF threshold for the Z1 high-pressure. All compressor stages will be unloaded
immediately if this is exceeded.
12..
60
60.0
bar
to Comp OFF Z2
XXX °C
tc-limit value for disable of
Z2 compressor capacity stages
-5..5
2
°C
to Comp ON Z2
XXX °C
tc-limit value for enable of
Z2 compressor capacity stages
-10..2
-2
°C
HP EMERG.-OFF
Z2
The EMERGENCY OFF threshold for the Z2 high-pressure. All compressor stages will be unloaded
immediately if this is exceeded.
12..
80
39
bar
to Comp OFF Z1
XXX °C
t -threshold for Z1 compressor disable
0
-54..2
-25
°C
to Comp OFF Z2
XXX °C
t -threshold for Z2 compressor disable
0
-54..2
-46
°C
Del. to OFF Z1
XXX m
Time delay for message
LP too low Z1
0..60
10
Min.
Del. to OFF Z2
XXX m
Time delay for message
LP too low Z2
0..60
10
Min.
Del. tc OFF XXX m
Time delay for message
HP too high
0..60
1
Min.
Min.tc/to diff XXX K
Minimum allowed difference between to and tc
5..15,
--
15
K
Starts/h XXX
Number of compressor switching operations per hour
4..16
6
-
standstill S1 Z1
XXX s
Minimum off time stage 1 (of Z1) for compressor combined control in Z1
30..
250
140
s
standstill S1 Z2
XXX s
Minimum off time stage 1 (of Z2) for compressor combined control in Z2
30..
250
140
s
Min.ÜH Z1 XXK
Setpoint minimum superheat Z1 on the pack side
2..15
4
K
Min.ÜH Z2 XXK
Setpoint minimum superheat Z2 on the pack side
2..15
4
K
delay min SH Z1
XXm
Setpoint delay time for message superheat too low Z1
1..30
10
Min.
delay min SH Z2
XXm
Setpoint delay time for message superheat too low Z2
1..30
10
Min.
Menu 3-4 Refrigerant monitoring
REFR. MON ID: XXXXX
Input
Default
Dim.
Del.low level
Time delay for refrigerant low liquid level message
---, 1..120
60
minutes