KGL Operating Manual – VS 3010 BS
2018-07-02
/
152 178
Menu 3-5 External alarms
EXT. ALARM ID: XXXXX
Input
Default
Dim.
Time delay XXX s
Time delay in seconds for
message
External Alarm
3..250
5
sec.
Alarm message:
XXXXXXXXXXXXXXXXXXX
Text that is displayed when external alarms occur:
Default text:
or
External Alarm
Speed Controller
Text
Menu 3-6 Base load
BASE LOAD ID:
XXXXX
Input
Default
Dim.
Cycle time C. Z1 XXX
m
Cycle time for the Z1 compressors base load rotation
5..
720
45
Min.
Cycle time C. Z2 XXX
m
Cycle time for the Z2 compressors base load rotation
5..
720
45
Min.
G.L.umsch.FU Z1 X
Activate base load rotation for Z1 fans
Y/N
N
-
G.L.umsch.FU Z2 X
Activate base load rotation for Z2 fans
Y/N
N
-
BaseLoadRot.F Y/N
Activate base load rotation for fans.
Only visible when the
type of HP control has been selected - screen 3-2-2-1-
"speed controller"
a
Y/N
N
-
On time cond. Y/N
Query for run time equalisation
Only visible if
is set to
BaseLoadRot.F
YES
Y/N
N
-
Cycle time F. XXX m
Cycle time for the fans base load rotation
Only visible if
is set to
BaseLoadRot.F
YES
5..
720
720
Min.
Menu 3 -7 Messages
Settings of the message priorities
Messages ID:
XXXXX
Input
Default
Dim.
Mot.cutout C Z2
X
Z2 compressor motor overload cutout tripped
-, 0..
99
2
-
Mot.cutout C Z1
X
Z1 compressor motor overload cutout tripped
-, 0..
99
2
-
Oil/HP fault Z2 X
Z2 compressor low oil pressure switch tripped
-, 0..
99
2
-
Oil/HP fault Z1 X
Z1 compressor low oil pressure switch tripped
-, 0..
99
2
-
Cyl.temp. Z2 X
Z2 cylinder head temperature threshold exceeded
-, 0..
99
2
-
Cyl.temp. Z1 X
Z1 cylinder head temperature threshold exceeded
-, 0..
99
2
-
Mot. cutout F X
Fan motor overload cutout tripped
-, 0..
99
2
-
HP cutout X
High-pressure cutout tripped
-, 0..
99
1
-
LP cutout Z2 X
Z2 low-pressure cutout tripped
-, 0..
99
2
-
LP cutout Z1 X
Z1 low-pressure cutout tripped
-, 0..
99
2
-
Low LP Z2 X
Lower threshold t0 Z2 undercut
-, 0..
99
2
-