KGL Operating Manual – UA 412 S
2019-01-14
/
90 122
ABTAUUNG POS: XXXXX
Input
Default
Wartezeit XX m
Setpoint wait time between cooling and defrost
0..15
0 m
Drip time x m
Setpoint delay time (drip time) between defrost and cooling
0..15
0 m
Menu 2-2-2 Sollwerte Umsch.
ABTAUUNG POS: XXXXX
Input
Default
Abtauendtemp XX °C
Setpoint defrost end temperature
--, 0..20
8 °C
Wartezeit XX m
Setpoint wait time between cooling and defrost
0..15
0 m
Drip time x m
Setpoint delay time (drip time) between defrost and cooling
0..15
0 m
Menu 2-3
Not applicable for this controller type.
Menu 2-4 Alarm
ALARM POS: XXXXX
1 Setpoints
Continue to menu 2-4-1
2 Sollwerte Umsch.
Continue to menu 2-4-2
is not displayed when toggle setpoint is deactivated (menu 3-3)
Menu 2-4-1 Setpoints
ALARM POS:
XXXXX
Input
Default
Soll Übertemp.
XX °C
High temperature setpoint at which the
is tripped.
high temperature alarm
0..30
10 °C
Soll Untertmp. XX
K
Setpoint temperature (difference below the setpoint of the temperature regulation) at which the
low
alarm is tripped
temperature
--, 0..
6
4 K
Menu 2-4-2 Sollwerte Umsch.
ALARM POS:
XXXXX
Input
Default
Soll Übertemp.
XX °C
High temperature setpoint at which the
is tripped.
high temperature alarm
0..30
10 °C
Soll Untertmp. XX
K
Setpoint temperature (difference below the setpoint of the temperature regulation) at which the
low
alarm is tripped
temperature
--, 0..
6
4 K
Menu 2-5 Frame heater
RAHMENHEIZ POS: XXXXX
1 Frame heater mode
Continue to menu 2-5-1
2 Frame heater setpoints
Continue to menu 2-5-2
3 Toggle mode
Continue to menu 2-5-3
is not displayed when toggle setpoint is deactivated (menu 3-3)
4 Sollwerte Umschal
Continue to menu 2-5-4
is not displayed when toggle setpoint is deactivated (menu 3-3)
Selection list 2-5-1 Frame heater mode
The value is selected in accordance with the entry. The check mark indicates the current setting.