KGL Operating Manual – UA 412 S
2019-01-14
/
108 122
REGLER POS: XXXXX
2 Temperature display
Continue to menu 6-2-2
3 Alarm delay
Continue to menu 6-2-3
4 230 V inputs
Continue to menu 6-2-4
5 Sensor type
Continue to menu 6-2-5
6 Analogue inputs
Continue to menu 6-2-6
7 Verfl.-Satz
Continue to menu 6-2-7
Menu 6-2-1 Type and version
VERSION POS: XXXXX
Input
Default
Controller type XXXXXXX
Controller type that is set using the DIP switch S3
–
SPIR410
Software Vers.: XXXX
Software version of the case controller
–
x.yy
Serial No.: XXXXXX
Serial number of the case controller
–
-
Master/Sl. Mode XXX
Synchronised defrost in the master / slave mode (ON/OFF)
–
-
Menu 6-2-2 Temperature display
ANZEIGE POS: XXXXX
Input
Default
Offset XX K
Offset for the display of the temperature
-10..10
0K
Alarm symbol X
Display of the alarm sysmbol in the temperature display of the BT30
,
, (Y, N)
N
Menu 6-2-3 Alarm delay
ALARMVERZ. POS: XXXXX
Input
Default
Sensor fault XX m
Alarm delay for sensor fault
0..30
15 min
Über/Unter Tmp XX m
Alarm delay for overtemperature / low temperature
0..120
60 min
No Defrost XX h
Alarm delay for no defrost
--, 2..168
24 h
Selfholding X
NO: Automatic reset of non-transient alarms.
YES: Alarms must be reset manually.
,
, (Y/N)
N
Menu 6-2-4 230 V inputs
230V EING. POS: XXXXX
Input
Default
Input 1: XXXXXXXXXX
Function of the digital input 1 terminals D11/D12
-
DEFROST TIMER
Input 2: XXXXXXXXXX
Function of the digital input 2 terminals D21/D22
-
SOLLW.UMSCH
Input 3: XXXXXXXXXX
Function of the digital input 3 terminals D31/D32
-
MANUAL OFF
Input 4: XXXXXXXXXX
Function of the digital input 4 terminals D41/D42
-
SICH.KETTE
Menu 6-2-5 Sensor type
Only the first sensors 1..5 (Z11/12..Z51/52) can be configured here - the sensors 6..10 (Z61/62..Z01
/Z02) are only for Pt1000.
The value is selected in accordance with the entry. The check mark indicates the current setting.