KGL Operating Manual – UA 412 S
2019-01-14
/
102 122
SOLLWERTE POS: XXXXX
3
Not applicable for this controller type
4 Alarm
Continue to menu 2-4
5 Frame heater
Continue to menu 2-5
Menu 2-1 Cooling
KÜHLUNG POS: XXXXX
1 Setpoints
Continue to menu 2-1-1
2 Sollwerte Umsch.
Continue to menu 2-1-2
is not displayed when toggle setpoint is deactivated (menu 3-3)
Menu 2-1-1 Setpoints
KÜHLUNG POS: XXXXX
Input
Default
Setpoint R2 xxx °C
Setpoint supply air temperature
-10..20
2 °C
Hysteresis R2 X K
Setpoint hysteresis supply air temperature
1..8
4 K
Setpoint R4 xxx °C
Setpoint return air temperature
-10..20
6 °C
Hysteresis R4 X K
Setpoint hysteresis return air temperature
1..8
2 K
Menu 2-1-2 Sollwerte Umsch.
KÜHLUNG POS: XXXXX
Input
Default
Setpoint R2 xxx °C
Setpoint supply air temperature
-10..20
4 °C
Hysteresis R2 X K
Setpoint hysteresis supply air temperature
1..8
4 K
Setpoint R4 xxx °C
Setpoint return air temperature
-10..20
5 °C
Hysteresis R4 X K
Setpoint hysteresis return air temperature
1..8
4 K
Menu 2-2 Defrost
ABTAUUNG POS: XXXXX
Input
1 Setpoints
Continue to menu 2-2-1
1
2 Sollwerte Umsch.
Continue to menu 2-2-2
is only displayed if two-zone operation is set (menu 6-1)
2
Menu 2-1-1 Setpoints
ABTAUUNG POS: XXXXX
Input
Default
Counting rate
Setpoint for the counting rate
0
0
Defrost counter
Setpoint for the defrost counter
0
0
Abtauendtemp XX °C
Setpoint defrost end temperature
--, 0..20
10 °C
Wartezeit XX m
Setpoint wait time between cooling and defrost
0..15
0 m
Drip time x m
Setpoint delay time (drip time) between defrost and cooling
0..15
0 m
Menu 2-2-2 Sollwerte Umsch.
ABTAUUNG POS: XXXXX
Input
Default
Counting rate
Setpoint for the counting rate
0
0
Defrost counter
Setpoint for the defrost counter
0
0